S7comm

S7comm is a telegraf external input plugin to gather data from Siemens PLC using the gos7 library.

Installation

Download the repo

git clone git@github.com:sakadda/s7comm.git

Change the poll interval if needed in the cmd/main.go file

var pollInterval = flag.Duration("poll_interval", 1*time.Second, "how often to send metrics")

Build the binary

go build -o s7comm cmd/main.go

Create your plugin.config file

[[inputs.s7comm]]
	name = "S7300"
	plc_ip = "192.168.10.57"
	plc_rack = 0
	plc_slot = 1
    	connect_timeout = "10s"
    	request_timeout = "2s"
    	nodes = [{name= "test_int", address= "DB1.DBW0", type = "int"},
        	{name= "test_real", address= "DB1.DBD2",type = "real"},
        	{name= "test_bool", address= "DB1.DBX10.0",type = "bool"},
        	{name= "test_dint", address= "DB1.DBD12",type = "dint"},
        	{name= "test_uint", address= "DB1.DBW16",type = "uint"},
        	{name= "test_udint", address= "DB1.DBD18",type = "udint"}]
Data Type Column 2 Column 3
bool Cell 2 Cell 3
byte Cell 5 Cell 6
dword Cell 8 Cell 9
int Cell 8 Cell 9
dint Cell 8 Cell 9
uint Cell 8 Cell 9
udint Cell 8 Cell 9
real Cell 8 Cell 9
float64 Cell 8 Cell 9
time Cell 8 Cell 9

From here, you can already test the plugin with your config file.

./s7comm -config plugin.conf
./s7comm.exe -config plugin.conf

If everything is ok, you should see something like this

test_int value=8056i 1623227848846884706
test_real value=403.14764404296875 1623227849849296642

Datatypes

You have to specifie the data type in your config file for each node. At the moment, only those types are implemented :

bool, byte, word, dword, int, dint, uint, udint, real, float64, time

Telegraf configuration

To use the plugin with telegraf, add this configuration to your main telegraf.conf file. S7comm is an external plugin using shim and execd. Go see their doc for more information.

# Run executable as long-running input plugin
[[inputs.execd]]
  ## One program to run as daemon.
  ## NOTE: process and each argument should each be their own string
  #command = ["telegraf-smartctl", "-d", "/dev/sda"]
command = ["/home/r/s7comm/s7comm", "-config", "/home/r/s7comm/CT.conf"]
  ## Environment variables
  ## Array of "key=value" pairs to pass as environment variables
  ## e.g. "KEY=value", "USERNAME=John Doe",
  ## "LD_LIBRARY_PATH=/opt/custom/lib64:/usr/local/libs"
  # environment = []

  ## Define how the process is signaled on each collection interval.
  ## Valid values are:
  ##   "none"    : Do not signal anything. (Recommended for service inputs)
  ##               The process must output metrics by itself.
  ##   "STDIN"   : Send a newline on STDIN. (Recommended for gather inputs)
  ##   "SIGHUP"  : Send a HUP signal. Not available on Windows. (not recommended)
  ##   "SIGUSR1" : Send a USR1 signal. Not available on Windows.
  ##   "SIGUSR2" : Send a USR2 signal. Not available on Windows.
  signal = "STDIN"

  ## Delay before the process is restarted after an unexpected termination
  restart_delay = "30s"

  ## Buffer size used to read from the command output stream
  ## Optional parameter. Default is 64 Kib, minimum is 16 bytes
  # buffer_size = "64Kib"

  ## Data format to consume.
  ## Each data format has its own unique set of configuration options, read
  ## more about them here:
  ## https://github.com/influxdata/telegraf/blob/master/docs/DATA_FORMATS_INPUT.md
  data_format = "influx"

PLC configuration

S7-300 and S7-400 usually use rack 0 and slot 2 and dont require additional configuration.

S7-1200 and S7-1500 usually use rack 0 and slot 1 and you need to enable the PUT/GET operations in the hardware configuration of your PLC and you have to set DBs as non-optimized.

Be aware of security issue. Once S7 Communication is enabled in a CPU, there is no way to block communication with a partner device. This means that any device on the same network can read and write data to the CPU using the S7 Communication protocol. For this reason, I would recommend using the native OPC.UA server for the newer S7-1200 and S7-1500 PLCs. See the OPC.UA telegraf plugin.

Contributing

Pull requests are welcome. For major changes, please open an issue first to discuss what you would like to change.

Please make sure to update tests as appropriate.