modbus

package
v1.33.0 Latest Latest
Warning

This package is not in the latest version of its module.

Go to latest
Published: Dec 9, 2024 License: MIT Imports: 19 Imported by: 0

README

Modbus Input Plugin

The Modbus plugin collects Discrete Inputs, Coils, Input Registers and Holding Registers via Modbus TCP or Modbus RTU/ASCII.

Global configuration options

In addition to the plugin-specific configuration settings, plugins support additional global and plugin configuration settings. These settings are used to modify metrics, tags, and field or create aliases and configure ordering, etc. See the CONFIGURATION.md for more details.

Configuration

# Retrieve data from MODBUS slave devices
[[inputs.modbus]]
  ## Connection Configuration
  ##
  ## The plugin supports connections to PLCs via MODBUS/TCP, RTU over TCP, ASCII over TCP or
  ## via serial line communication in binary (RTU) or readable (ASCII) encoding
  ##
  ## Device name
  name = "Device"

  ## Slave ID - addresses a MODBUS device on the bus
  ## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
  slave_id = 1

  ## Timeout for each request
  timeout = "1s"

  ## Maximum number of retries and the time to wait between retries
  ## when a slave-device is busy.
  # busy_retries = 0
  # busy_retries_wait = "100ms"

  # TCP - connect via Modbus/TCP
  controller = "tcp://localhost:502"

  ## Serial (RS485; RS232)
  ## For RS485 specific setting check the end of the configuration.
  ## For unix-like operating systems use:
  # controller = "file:///dev/ttyUSB0"
  ## For Windows operating systems use:
  # controller = "COM1"
  # baud_rate = 9600
  # data_bits = 8
  # parity = "N"
  # stop_bits = 1

  ## Transmission mode for Modbus packets depending on the controller type.
  ## For Modbus over TCP you can choose between "TCP" , "RTUoverTCP" and
  ## "ASCIIoverTCP".
  ## For Serial controllers you can choose between "RTU" and "ASCII".
  ## By default this is set to "auto" selecting "TCP" for ModbusTCP connections
  ## and "RTU" for serial connections.
  # transmission_mode = "auto"

  ## Trace the connection to the modbus device
  # log_level = "trace"

  ## Define the configuration schema
  ##  |---register -- define fields per register type in the original style (only supports one slave ID)
  ##  |---request  -- define fields on a requests base
  ##  |---metric   -- define fields on a metric base
  configuration_type = "register"

  ## Exclude the register type tag
  ## Please note, this will also influence the grouping of metrics as you won't
  ## see one metric per register type anymore!
  # exclude_register_type_tag = false

  ## --- "register" configuration style ---

  ## Measurements
  ##

  ## Digital Variables, Discrete Inputs and Coils
  ## measurement - the (optional) measurement name, defaults to "modbus"
  ## name        - the variable name
  ## data_type   - the (optional) output type, can be BOOL or UINT16 (default)
  ## address     - variable address

  discrete_inputs = [
    { name = "start",          address = [0]},
    { name = "stop",           address = [1]},
    { name = "reset",          address = [2]},
    { name = "emergency_stop", address = [3]},
  ]
  coils = [
    { name = "motor1_run",     address = [0]},
    { name = "motor1_jog",     address = [1]},
    { name = "motor1_stop",    address = [2]},
  ]

  ## Analog Variables, Input Registers and Holding Registers
  ## measurement - the (optional) measurement name, defaults to "modbus"
  ## name        - the variable name
  ## byte_order  - the ordering of bytes
  ##  |---AB, ABCD   - Big Endian
  ##  |---BA, DCBA   - Little Endian
  ##  |---BADC       - Mid-Big Endian
  ##  |---CDAB       - Mid-Little Endian
  ## data_type   - BIT (single bit of a register)
  ##               INT8L, INT8H, UINT8L, UINT8H (low and high byte variants)
  ##               INT16, UINT16, INT32, UINT32, INT64, UINT64,
  ##               FLOAT16-IEEE, FLOAT32-IEEE, FLOAT64-IEEE (IEEE 754 binary representation)
  ##               FIXED, UFIXED (fixed-point representation on input)
  ##               STRING (byte-sequence converted to string)
  ## bit         - (optional) bit of the register, ONLY valid for BIT type
  ## scale       - the final numeric variable representation
  ## address     - variable address

  holding_registers = [
    { name = "power_factor", byte_order = "AB",   data_type = "FIXED", scale=0.01,  address = [8]},
    { name = "voltage",      byte_order = "AB",   data_type = "FIXED", scale=0.1,   address = [0]},
    { name = "energy",       byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [5,6]},
    { name = "current",      byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [1,2]},
    { name = "frequency",    byte_order = "AB",   data_type = "UFIXED", scale=0.1,  address = [7]},
    { name = "power",        byte_order = "ABCD", data_type = "UFIXED", scale=0.1,  address = [3,4]},
    { name = "firmware",     byte_order = "AB",   data_type = "STRING", address = [5, 6, 7, 8, 9, 10, 11, 12]},
  ]
  input_registers = [
    { name = "tank_level",   byte_order = "AB",   data_type = "INT16",   scale=1.0,     address = [0]},
    { name = "tank_ph",      byte_order = "AB",   data_type = "INT16",   scale=1.0,     address = [1]},
    { name = "pump1_speed",  byte_order = "ABCD", data_type = "INT32",   scale=1.0,     address = [3,4]},
  ]

  ## --- "request" configuration style ---

  ## Per request definition
  ##

  ## Define a request sent to the device
  ## Multiple of those requests can be defined. Data will be collated into metrics at the end of data collection.
  [[inputs.modbus.request]]
    ## ID of the modbus slave device to query.
    ## If you need to query multiple slave-devices, create several "request" definitions.
    slave_id = 1

    ## Byte order of the data.
    ##  |---ABCD -- Big Endian (Motorola)
    ##  |---DCBA -- Little Endian (Intel)
    ##  |---BADC -- Big Endian with byte swap
    ##  |---CDAB -- Little Endian with byte swap
    byte_order = "ABCD"

    ## Type of the register for the request
    ## Can be "coil", "discrete", "holding" or "input"
    register = "coil"

    ## Name of the measurement.
    ## Can be overridden by the individual field definitions. Defaults to "modbus"
    # measurement = "modbus"

    ## Request optimization algorithm.
    ##  |---none       -- Do not perform any optimization and use the given layout(default)
    ##  |---shrink     -- Shrink requests to actually requested fields
    ##  |                 by stripping leading and trailing omits
    ##  |---rearrange  -- Rearrange request boundaries within consecutive address ranges
    ##  |                 to reduce the number of requested registers by keeping
    ##  |                 the number of requests.
    ##  |---max_insert -- Rearrange request keeping the number of extra fields below the value
    ##                    provided in "optimization_max_register_fill". It is not necessary to define 'omitted'
    ##                    fields as the optimisation will add such field only where needed.
    # optimization = "none"

    ## Maximum number register the optimizer is allowed to insert between two fields to
    ## save requests.
    ## This option is only used for the 'max_insert' optimization strategy.
    ## NOTE: All omitted fields are ignored, so this option denotes the effective hole
    ## size to fill.
    # optimization_max_register_fill = 50

    ## Field definitions
    ## Analog Variables, Input Registers and Holding Registers
    ## address        - address of the register to query. For coil and discrete inputs this is the bit address.
    ## name *1        - field name
    ## type *1,2      - type of the modbus field, can be
    ##                  BIT (single bit of a register)
    ##                  INT8L, INT8H, UINT8L, UINT8H (low and high byte variants)
    ##                  INT16, UINT16, INT32, UINT32, INT64, UINT64 and
    ##                  FLOAT16, FLOAT32, FLOAT64 (IEEE 754 binary representation)
    ##                  STRING (byte-sequence converted to string)
    ## length *1,2    - (optional) number of registers, ONLY valid for STRING type
    ## bit *1,2       - (optional) bit of the register, ONLY valid for BIT type
    ## scale *1,2,4   - (optional) factor to scale the variable with
    ## output *1,3,4  - (optional) type of resulting field, can be INT64, UINT64 or FLOAT64.
    ##                  Defaults to FLOAT64 for numeric fields if "scale" is provided.
    ##                  Otherwise the input "type" class is used (e.g. INT* -> INT64).
    ## measurement *1 - (optional) measurement name, defaults to the setting of the request
    ## omit           - (optional) omit this field. Useful to leave out single values when querying many registers
    ##                  with a single request. Defaults to "false".
    ##
    ## *1: These fields are ignored if field is omitted ("omit"=true)
    ## *2: These fields are ignored for both "coil" and "discrete"-input type of registers.
    ## *3: This field can only be "UINT16" or "BOOL" if specified for both "coil"
    ##     and "discrete"-input type of registers. By default the fields are
    ##     output as zero or one in UINT16 format unless "BOOL" is used.
    ## *4: These fields cannot be used with "STRING"-type fields.

    ## Coil / discrete input example
    fields = [
      { address=0, name="motor1_run" },
      { address=1, name="jog", measurement="motor" },
      { address=2, name="motor1_stop", omit=true },
      { address=3, name="motor1_overheating", output="BOOL" },
      { address=4, name="firmware", type="STRING", length=8 },
    ]

    [inputs.modbus.request.tags]
      machine = "impresser"
      location = "main building"

  [[inputs.modbus.request]]
    ## Holding example
    ## All of those examples will result in FLOAT64 field outputs
    slave_id = 1
    byte_order = "DCBA"
    register = "holding"
    fields = [
      { address=0, name="voltage",      type="INT16",   scale=0.1   },
      { address=1, name="current",      type="INT32",   scale=0.001 },
      { address=3, name="power",        type="UINT32",  omit=true   },
      { address=5, name="energy",       type="FLOAT32", scale=0.001, measurement="W" },
      { address=7, name="frequency",    type="UINT32",  scale=0.1   },
      { address=8, name="power_factor", type="INT64",   scale=0.01  },
    ]

    [inputs.modbus.request.tags]
      machine = "impresser"
      location = "main building"

  [[inputs.modbus.request]]
    ## Input example with type conversions
    slave_id = 1
    byte_order = "ABCD"
    register = "input"
    fields = [
      { address=0, name="rpm",         type="INT16"                   },  # will result in INT64 field
      { address=1, name="temperature", type="INT16", scale=0.1        },  # will result in FLOAT64 field
      { address=2, name="force",       type="INT32", output="FLOAT64" },  # will result in FLOAT64 field
      { address=4, name="hours",       type="UINT32"                  },  # will result in UIN64 field
    ]

    [inputs.modbus.request.tags]
      machine = "impresser"
      location = "main building"

  ## --- "metric" configuration style ---

  ## Per metric definition
  ##

  ## Request optimization algorithm across metrics
  ##  |---none       -- Do not perform any optimization and just group requests
  ##  |                 within metrics (default)
  ##  |---max_insert -- Collate registers across all defined metrics and fill in
  ##                    holes to optimize the number of requests.
  # optimization = "none"

  ## Maximum number of registers the optimizer is allowed to insert between
  ## non-consecutive registers to save requests.
  ## This option is only used for the 'max_insert' optimization strategy and
  ## effectively denotes the hole size between registers to fill.
  # optimization_max_register_fill = 50

  ## Define a metric produced by the requests to the device
  ## Multiple of those metrics can be defined. The referenced registers will
  ## be collated into requests send to the device
  [[inputs.modbus.metric]]
    ## ID of the modbus slave device to query
    ## If you need to query multiple slave-devices, create several "metric" definitions.
    slave_id = 1

    ## Byte order of the data
    ##  |---ABCD -- Big Endian (Motorola)
    ##  |---DCBA -- Little Endian (Intel)
    ##  |---BADC -- Big Endian with byte swap
    ##  |---CDAB -- Little Endian with byte swap
    # byte_order = "ABCD"

    ## Name of the measurement
    # measurement = "modbus"

    ## Field definitions
    ## register    - type of the modbus register, can be "coil", "discrete",
    ##               "holding" or "input". Defaults to "holding".
    ## address     - address of the register to query. For coil and discrete inputs this is the bit address.
    ## name        - field name
    ## type *1     - type of the modbus field, can be
    ##                 BIT (single bit of a register)
    ##                 INT8L, INT8H, UINT8L, UINT8H (low and high byte variants)
    ##                 INT16, UINT16, INT32, UINT32, INT64, UINT64 and
    ##                 FLOAT16, FLOAT32, FLOAT64 (IEEE 754 binary representation)
    ##                 STRING (byte-sequence converted to string)
    ## length *1   - (optional) number of registers, ONLY valid for STRING type
    ## bit *1,2    - (optional) bit of the register, ONLY valid for BIT type
    ## scale *1,3  - (optional) factor to scale the variable with
    ## output *2,3 - (optional) type of resulting field, can be INT64, UINT64 or FLOAT64. Defaults to FLOAT64 if
    ##               "scale" is provided and to the input "type" class otherwise (i.e. INT* -> INT64, etc).
    ##
    ## *1: These fields are ignored for both "coil" and "discrete"-input type of registers.
    ## *2: This field can only be "UINT16" or "BOOL" if specified for both "coil"
    ##     and "discrete"-input type of registers. By default the fields are
    ##     output as zero or one in UINT16 format unless "BOOL" is used.
    ## *3: These fields cannot be used with "STRING"-type fields.
    fields = [
      { register="coil",    address=0, name="door_open"},
      { register="coil",    address=1, name="status_ok"},
      { register="holding", address=0, name="voltage",      type="INT16"   },
      { address=1, name="current",      type="INT32",   scale=0.001 },
      { address=5, name="energy",       type="FLOAT32", scale=0.001 },
      { address=7, name="frequency",    type="UINT32",  scale=0.1   },
      { address=8, name="power_factor", type="INT64",   scale=0.01  },
      { address=9, name="firmware",     type="STRING",  length=8    },
    ]

    ## Tags assigned to the metric
    # [inputs.modbus.metric.tags]
    #   machine = "impresser"
    #   location = "main building"

  ## RS485 specific settings. Only take effect for serial controllers.
  ## Note: This has to be at the end of the modbus configuration due to
  ## TOML constraints.
  # [inputs.modbus.rs485]
    ## Delay RTS prior to sending
    # delay_rts_before_send = "0ms"
    ## Delay RTS after to sending
    # delay_rts_after_send = "0ms"
    ## Pull RTS line to high during sending
    # rts_high_during_send = false
    ## Pull RTS line to high after sending
    # rts_high_after_send = false
    ## Enabling receiving (Rx) during transmission (Tx)
    # rx_during_tx = false

  ## Enable workarounds required by some devices to work correctly
  # [inputs.modbus.workarounds]
    ## Pause after connect delays the first request by the specified time.
    ## This might be necessary for (slow) devices.
    # pause_after_connect = "0ms"

    ## Pause between read requests sent to the device.
    ## This might be necessary for (slow) serial devices.
    # pause_between_requests = "0ms"

    ## Close the connection after every gather cycle.
    ## Usually the plugin closes the connection after a certain idle-timeout,
    ## however, if you query a device with limited simultaneous connectivity
    ## (e.g. serial devices) from multiple instances you might want to only
    ## stay connected during gather and disconnect afterwards.
    # close_connection_after_gather = false

    ## Force the plugin to read each field in a separate request.
    ## This might be necessary for devices not conforming to the spec,
    ## see https://github.com/influxdata/telegraf/issues/12071.
    # one_request_per_field = false

    ## Enforce the starting address to be zero for the first request on
    ## coil registers. This is necessary for some devices see
    ## https://github.com/influxdata/telegraf/issues/8905
    # read_coils_starting_at_zero = false

    ## String byte-location in registers AFTER byte-order conversion
    ## Some device (e.g. EM340) place the string byte in only the upper or
    ## lower byte location of a register see
    ## https://github.com/influxdata/telegraf/issues/14748
    ## Available settings:
    ##   lower -- use only lower byte of the register i.e. 00XX 00XX 00XX 00XX
    ##   upper -- use only upper byte of the register i.e. XX00 XX00 XX00 XX00
    ## By default both bytes of the register are used i.e. XXXX XXXX.
    # string_register_location = ""

Notes

You can debug Modbus connection issues by enabling debug_connection. To see those debug messages, Telegraf has to be started with debugging enabled (i.e. with the --debug option). Please be aware that connection tracing will produce a lot of messages and should NOT be used in production environments.

Please use pause_after_connect / pause_between_requests with care. Ensure the total gather time, including the pause(s), does not exceed the configured collection interval. Note that pauses add up if multiple requests are sent!

Configuration styles

The modbus plugin supports multiple configuration styles that can be set using the configuration_type setting. The different styles are described below. Please note that styles cannot be mixed, i.e. only the settings belonging to the configured configuration_type are used for constructing modbus requests and creation of metrics.

Directly jump to the styles:


register configuration style

This is the original style used by this plugin. It allows a per-register configuration for a single slave-device.

[!NOTE] _For legacy reasons this configuration style is not completely consistent with the other styles.

Usage of data_type

The field data_type defines the representation of the data value on input from the modbus registers. The input values are then converted from the given data_type to a type that is appropriate when sending the value to the output plugin. These output types are usually an integer or floating-point-number. The size of the output type is assumed to be large enough for all supported input types. The mapping from the input type to the output type is fixed and cannot be configured.

Booleans: BOOL

This type is only valid for coil and discrete registers. The value will be true if the register has a non-zero (ON) value and false otherwise.

Integers: INT8L, INT8H, UINT8L, UINT8H

These types are used for 8-bit integer values. Select the one that matches your modbus data source. The L and H suffix denotes the low- and high byte of the register respectively.

Integers: INT16, UINT16, INT32, UINT32, INT64, UINT64

These types are used for integer input values. Select the one that matches your modbus data source. For coil and discrete registers only UINT16 is valid.

Floating Point: FLOAT16-IEEE, FLOAT32-IEEE, FLOAT64-IEEE

Use these types if your modbus registers contain a value that is encoded in this format. These types always include the sign, therefore no variant exists.

Fixed Point: FIXED, UFIXED

These types are handled as an integer type on input, but are converted to floating point representation for further processing (e.g. scaling). Use one of these types when the input value is a decimal fixed point representation of a non-integer value.

Select the type UFIXED when the input type is declared to hold unsigned integer values, which cannot be negative. The documentation of your modbus device should indicate this by a term like 'uint16 containing fixed-point representation with N decimal places'.

Select the type FIXED when the input type is declared to hold signed integer values. Your documentation of the modbus device should indicate this with a term like 'int32 containing fixed-point representation with N decimal places'.

String: STRING

This type is used to query the number of registers specified in the address setting and convert the byte-sequence to a string. Please note, if the byte-sequence contains a null byte, the string is truncated at this position. You cannot use the scale setting for string fields.

Bit: BIT

This type is used to query a single bit of a register specified in the address setting and convert the value to an unsigned integer. This type requires the bit setting to be specified.


request configuration style

This style can be used to specify the modbus requests directly. It enables specifying multiple [[inputs.modbus.request]] sections including multiple slave-devices. This way, modbus gateway devices can be queried. Please note that requests might be split for non-consecutive addresses. If you want to avoid this behavior please add fields with the omit flag set filling the gaps between addresses.

Slave device

You can use the slave_id setting to specify the ID of the slave device to query. It should be specified for each request, otherwise it defaults to zero. Please note, only one slave_id can be specified per request.

Byte order of the register

The byte_order setting specifies the byte and word-order of the registers. It can be set to ABCD for big endian (Motorola) or DCBA for little endian (Intel) format as well as BADC and CDAB for big endian or little endian with byte swap.

Register type

The register setting specifies the modbus register-set to query and can be set to coil, discrete, holding or input.

Per-request measurement setting

You can specify the name of the measurement for the following field definitions using the measurement setting. If the setting is omitted modbus is used. Furthermore, the measurement value can be overridden by each field individually.

Optimization setting

Please only use request optimization if you do understand the implications! The optimization setting can be used to optimize the actual requests sent to the device. The following algorithms are available

none (default)

Do not perform any optimization. Please note that the requests are still obeying the maximum request sizes. Furthermore, completely empty requests, i.e. all fields specify omit=true, are removed. Otherwise, the requests are sent as specified by the user including request of omitted fields. This setting should be used if you want full control over the requests e.g. to accommodate for device constraints.

shrink

This optimization allows to remove leading and trailing fields from requests if those fields are omitted. This can shrink the request number and sizes in cases where you specify large amounts of omitted fields, e.g. for documentation purposes.

rearrange

Requests are processed similar to shrink but the request boundaries are rearranged such that usually less registers are being read while keeping the number of requests. This optimization algorithm only works on consecutive address ranges and respects user-defined gaps in the field addresses.

Please note: This optimization might take long in case of many non-consecutive, non-omitted fields!

aggressive

Requests are processed similar to rearrange but user-defined gaps in the field addresses are filled automatically. This usually reduces the number of requests, but will increase the number of registers read due to larger requests. This algorithm might be useful if you only want to specify the fields you are interested in but want to minimize the number of requests sent to the device.

Please note: This optimization might take long in case of many non-consecutive, non-omitted fields!

max_insert

Fields are assigned to the same request as long as the hole between the fields do not exceed the maximum fill size given in optimization_max_register_fill. User-defined omitted fields are ignored and interpreted as holes, so the best practice is to not manually insert omitted fields for this optimizer. This allows to specify only actually used fields and let the optimizer figure out the request organization which can dramatically improve query time. The trade-off here is between the cost of reading additional registers trashed later and the cost of many requests.

Please note: The optimal value for optimization_max_register_fill depends on the network and the queried device. It is hence recommended to test several values and assess performance in order to find the best value. Use the --test --debug flags to monitor how may requests are sent and the number of touched registers.

Field definitions

Each request can contain a list of fields to collect from the modbus device.

address

A field is identified by an address that reflects the modbus register address. You can usually find the address values for the different data-points in the datasheet of your modbus device. This is a mandatory setting.

For coil and discrete input registers this setting specifies the bit containing the value of the field.

name

Using the name setting you can specify the field-name in the metric as output by the plugin. This setting is ignored if the field's omit is set to true and can be omitted in this case.

Please note: There cannot be multiple fields with the same name in one metric identified by measurement, slave_id and register.

register datatype

The type setting specifies the datatype of the modbus register and can be set to INT8L, INT8H, UINT8L, UINT8H where L is the lower byte of the register and H is the higher byte. Furthermore, the types INT16, UINT16, INT32, UINT32, INT64 or UINT64 for integer types or FLOAT16, FLOAT32 and FLOAT64 for IEEE 754 binary representations of floating point values exist. FLOAT16 denotes a half-precision float with a 16-bit representation. Usually the datatype of the register is listed in the datasheet of your modbus device in relation to the address described above.

The STRING datatype is special in that it requires the length setting to be specified containing the length (in terms of number of registers) containing the string. The returned byte-sequence is interpreted as string and truncated to the first null byte found if any. The scale and output setting cannot be used for this type.

This setting is ignored if the field's omit is set to true or if the register type is a bit-type (coil or discrete) and can be omitted in these cases.

scaling

You can use the scale setting to scale the register values, e.g. if the register contains a fix-point values in UINT32 format with two decimal places for example. To convert the read register value to the actual value you can set the scale=0.01. The scale is used as a factor e.g. field_value * scale.

This setting is ignored if the field's omit is set to true or if the register type is a bit-type (coil or discrete) and can be omitted in these cases.

Please note: The resulting field-type will be set to FLOAT64 if no output format is specified.

output datatype

Using the output setting you can explicitly specify the output field-datatype. The output type can be INT64, UINT64 or FLOAT64. If not set explicitly, the output type is guessed as follows: If scale is set to a non-zero value, the output type is FLOAT64. Otherwise, the output type corresponds to the register datatype class, i.e. INT* will result in INT64, UINT* in UINT64 and FLOAT* in FLOAT64.

This setting is ignored if the field's omit is set to true and can be omitted. In case the register type is a bit-type (coil or discrete) only UINT16 or BOOL are valid with the former being the default if omitted. For coil and discrete registers the field-value is output as zero or one in UINT16 format or as true and false in BOOL format.

per-field measurement setting

The measurement setting can be used to override the measurement name on a per-field basis. This might be useful if you want to split the fields in one request to multiple measurements. If not specified, the value specified in the request section or, if also omitted, modbus is used.

This setting is ignored if the field's omit is set to true and can be omitted in this case.

omitting a field

When specifying omit=true, the corresponding field will be ignored when collecting the metric but is taken into account when constructing the modbus requests. This way, you can fill "holes" in the addresses to construct consecutive address ranges resulting in a single request. Using a single modbus request can be beneficial as the values are all collected at the same point in time.

Tags definitions

Each request can be accompanied by tags valid for this request.

Please note: These tags take precedence over predefined tags such as name, type or slave_id.


metric configuration style

This style can be used to specify the desired metrics directly instead of focusing on the modbus view. Multiple [[inputs.modbus.metric]] sections including multiple slave-devices can be specified. This way, modbus gateway devices can be queried. The plugin automatically collects registers across the specified metrics, groups them per slave and register-type and (optionally) optimizes the resulting requests for non-consecutive addresses.

Slave device

You can use the slave_id setting to specify the ID of the slave device to query. It should be specified for each metric section, otherwise it defaults to zero. Please note, only one slave_id can be specified per metric section.

Byte order of the registers

The byte_order setting specifies the byte and word-order of the registers. It can be set to ABCD for big endian (Motorola) or DCBA for little endian (Intel) format as well as BADC and CDAB for big endian or little endian with byte swap.

Measurement name

You can specify the name of the measurement for the fields defined in the given section using the measurement setting. If the setting is omitted modbus is used.

Optimization setting

Please only use request optimization if you do understand the implications! The optimization setting can specified globally, i.e. NOT per metric section, and is used to optimize the actual requests sent to the device. Here, the optimization is applied across all metric sections! The following algorithms are available

none (default)

Do not perform any optimization. Please note that consecutive registers are still grouped into one requests while obeying the maximum request sizes. This setting should be used if you want to touch as less registers as possible at the cost of more requests sent to the device.

max_insert

Fields are assigned to the same request as long as the hole between the touched registers does not exceed the maximum fill size given via optimization_max_register_fill. This optimization might lead to a drastically reduced request number and thus an improved query time. The trade-off here is between the cost of reading additional registers trashed later and the cost of many requests.

Please note: The optimal value for optimization_max_register_fill depends on the network and the queried device. It is hence recommended to test several values and assess performance in order to find the best value. Use the --test --debug flags to monitor how may requests are sent and the number of touched registers.

Field definitions

Each metric can contain a list of fields to collect from the modbus device. The specified fields directly corresponds to the fields of the resulting metric.

register

The register setting specifies the modbus register-set to query and can be set to coil, discrete, holding or input.

address

A field is identified by an address that reflects the modbus register address. You can usually find the address values for the different data-points in the datasheet of your modbus device. This is a mandatory setting.

For coil and discrete input registers this setting specifies the bit containing the value of the field.

name

Using the name setting you can specify the field-name in the metric as output by the plugin.

Please note: There cannot be multiple fields with the same name in one metric identified by measurement, slave_id, register and tag-set.

register datatype

The type setting specifies the datatype of the modbus register and can be set to INT8L, INT8H, UINT8L, UINT8H where L is the lower byte of the register and H is the higher byte. Furthermore, the types INT16, UINT16, INT32, UINT32, INT64 or UINT64 for integer types or FLOAT16, FLOAT32 and FLOAT64 for IEEE 754 binary representations of floating point values exist. FLOAT16 denotes a half-precision float with a 16-bit representation. Usually the datatype of the register is listed in the datasheet of your modbus device in relation to the address described above.

The STRING datatype is special in that it requires the length setting to be specified containing the length (in terms of number of registers) containing the string. The returned byte-sequence is interpreted as string and truncated to the first null byte found if any. The scale and output setting cannot be used for this type.

This setting is ignored if the register is a bit-type (coil or discrete) and can be omitted in these cases.

scaling

You can use the scale setting to scale the register values, e.g. if the register contains a fix-point values in UINT32 format with two decimal places for example. To convert the read register value to the actual value you can set the scale=0.01. The scale is used as a factor e.g. field_value * scale.

This setting is ignored if the register is a bit-type (coil or discrete) and can be omitted in these cases.

Please note: The resulting field-type will be set to FLOAT64 if no output format is specified.

output datatype

Using the output setting you can explicitly specify the output field-datatype. The output type can be INT64, UINT64 or FLOAT64. If not set explicitly, the output type is guessed as follows: If scale is set to a non-zero value, the output type is FLOAT64. Otherwise, the output type corresponds to the register datatype class, i.e. INT* will result in INT64, UINT* in UINT64 and FLOAT* in FLOAT64.

In case the register is a bit-type (coil or discrete) only UINT16 or BOOL are valid with the former being the default if omitted. For coil and discrete registers the field-value is output as zero or one in UINT16 format or as true and false in BOOL format.

Tags definitions

Each metric can be accompanied by a set of tag. These tags directly correspond to the tags of the resulting metric.

Please note: These tags take precedence over predefined tags such as name, type or slave_id.


Metrics

Metrics are custom and configured using the discrete_inputs, coils, holding_register and input_registers options.

Troubleshooting

Strange data

Modbus documentation is often a mess. People confuse memory-address (starts at one) and register address (starts at zero) or are unsure about the word-order used. Furthermore, there are some non-standard implementations that also swap the bytes within the register word (16-bit).

If you get an error or don't get the expected values from your device, you can try the following steps (assuming a 32-bit value).

If you are using a serial device and get a permission denied error, check the permissions of your serial device and change them accordingly.

In case you get an exception '2' (illegal data address) error you might try to offset your address entries by minus one as it is very likely that there is confusion between memory and register addresses.

If you see strange values, the byte_order might be wrong. You can either probe all combinations (ABCD, CDBA, BADC or DCBA) or set byte_order="ABCD" data_type="UINT32" and use the resulting value(s) in an online converter like this. This especially makes sense if you don't want to mess with the device, deal with 64-bit values and/or don't know the data_type of your register (e.g. fix-point floating values vs. IEEE floating point).

If your data still looks corrupted, please post your configuration, error message and/or the output of byte_order="ABCD" data_type="UINT32" to one of the telegraf support channels (forum, slack or as an issue). If nothing helps, please post your configuration, error message and/or the output of byte_order="ABCD" data_type="UINT32" to one of the telegraf support channels (forum, slack or as an issue).

Workarounds

Some Modbus devices need special read characteristics when reading data and will fail otherwise. For example, some serial devices need a pause between register read requests. Others might only support a limited number of simultaneously connected devices, like serial devices or some ModbusTCP devices. In case you need to access those devices in parallel you might want to disconnect immediately after the plugin finishes reading.

To enable this plugin to also handle those "special" devices, there is the workarounds configuration option. In case your documentation states certain read requirements or you get read timeouts or other read errors, you might want to try one or more workaround options. If you find that other/more workarounds are required for your device, please let us know.

In case your device needs a workaround that is not yet implemented, please open an issue or submit a pull-request.

Example Output

modbus.InputRegisters,host=orangepizero Current=0,Energy=0,Frequency=60,Power=0,PowerFactor=0,Voltage=123.9000015258789 1554079521000000000

Documentation

Index

Constants

This section is empty.

Variables

This section is empty.

Functions

This section is empty.

Types

type Modbus

type Modbus struct {
	Name                   string          `toml:"name"`
	Controller             string          `toml:"controller"`
	TransmissionMode       string          `toml:"transmission_mode"`
	BaudRate               int             `toml:"baud_rate"`
	DataBits               int             `toml:"data_bits"`
	Parity                 string          `toml:"parity"`
	StopBits               int             `toml:"stop_bits"`
	RS485                  *rs485Config    `toml:"rs485"`
	Timeout                config.Duration `toml:"timeout"`
	Retries                int             `toml:"busy_retries"`
	RetriesWaitTime        config.Duration `toml:"busy_retries_wait"`
	DebugConnection        bool            `toml:"debug_connection" deprecated:"1.35.0;use 'log_level' 'trace' instead"`
	Workarounds            workarounds     `toml:"workarounds"`
	ConfigurationType      string          `toml:"configuration_type"`
	ExcludeRegisterTypeTag bool            `toml:"exclude_register_type_tag"`
	Log                    telegraf.Logger `toml:"-"`
	// contains filtered or unexported fields
}

func (*Modbus) Gather

func (m *Modbus) Gather(acc telegraf.Accumulator) error

func (*Modbus) Init

func (m *Modbus) Init() error

func (*Modbus) Printf added in v1.21.0

func (m *Modbus) Printf(format string, v ...interface{})

Printf implements the logger interface of the modbus client

func (*Modbus) SampleConfig

func (m *Modbus) SampleConfig() string

Jump to

Keyboard shortcuts

? : This menu
/ : Search site
f or F : Jump to
y or Y : Canonical URL